38
Table 10.1
Bi-Flame Operating Sequence (continued)
BURNER START-UP (continued)
Is flame signal present ?
NO
Modulator sent to automatic 20
seconds after main valve is
energized.
Pilot will shut off 10 seconds
after main flame is energized.
Flame signal = XX.X Volts DC;
(X) = Number of burner being
monitored; the Bi-Flame will
scroll through each burner con-
tinuously during the burner-on
cycle.
YES
X = burner number.
ERROR MESSAGE
MAIN # (OX) FAILED
AUTOMATIC
MODULATION
NORMAL MESSAGE
NORMAL MESSAGE
FLAME #(OX) XX.XV
TIME = XXXX:XX:XX
IF Interrupted Pilot is selected
NORMAL MESSAGE
MAIN FLAME ON
PILOT OFF
NORMAL MESSAGE
MAIN FLAME ON